RAISED ACCESS FLOORS: PANELS

GWI/S

HD Calcium Sulphate Steel Encapsulated

EUROPEAN PATENT N.1409812

Elevated fl oor panel GWI/S encapsulated in galvanized pressed steel. Structural reinforcement is recessed and vertical around the entire perimeter, composed of two closed semi-capsules for double overlap and edge clipping. Formation of a micro perimeter expansion area. Insert made of calcium sulfate

TEST

Product Highlights

  • Excellent fire resistance with A1FL classification and REI 120′.
  • Exceptional acoustic insulation with airborne noise attenuation > 38 dB and vertical noise reduction > 33 dB.
  • Robust structure with a calcium sulfate core of 1600 kg/m³ density.
  • Advanced mechanical performance, with concentrated load up to 7.60 kN and distributed load up to 45.00 kN/m².

TECHNICAL AREA

PHYSICAL CHARACTERISTICS Without Surface Coating
CharacteristicsValueStandard
Dimensions600×600 mmEN 12825
Nominal Thickness29.30 mmEN 12825
Panel CoreCalcium sulfate, density 1600 kg/m³ ±5% 
Weight18.3 kg 
Flexion2.5 mm, Class AEN 12825
FIRE AND ELECTRICAL PERFORMANCE
CharacteristicsValueStandard
Fire ReactionA1FLUNI EN 13501-1
Fire ResistanceREI 120′UNI EN 13501-2
Electrical Resistance≥ 107 ΩEN 1081
ACOUSTIC PERFORMANCE
CharacteristicsValueStandard
Horizontal Airborne Noise Reduction> 38 dBUNI EN ISO 140-12
Vertical Impact Noise Reduction> 33 dBUNI EN ISO 140-8
MECHANICAL CHARACTERISTICS (EN 12825)
COMPARATIVE WITH STRUCTURES
System Type GWIS – SA GWIS – ST1 GWIS – ST2 GWIS – STH GWIS – 50S
Support Structures TF3/SA only pedestals TF3/ST1 Crossbars 18x28x18 mm TF3/ST2 Crossbars 38x28x38 mm TF3/STH Closed section crossbars 25×25 mm TF2/50S Closed section crossbars 50×25 mm, lengths 549 mm, 1800 mm
System Weight Without Coverings 52.65 kg/m² 54.24 kg/m² 54.94 kg/m² 55.08 kg/m² 56.95 kg/m²
Axial Compression on Pedestal > 24.00 kN > 24.00 kN > 24.00 kN > 24.00 kN > 24.00 kN
Maximum Breaking Load 15.40 kN 15.40 kN 15.60 kN 17.10 kN 18.40 kN
Overall Load Class (EN) 6 A 6 A 6 A 6 A 6 A
Concentrated Load 6.20 kN 6.20 kN 6.90 kN 7.60 kN 8.50 kN
Distributed Load 31.20 kN/m² 31.20 kN/m² 35.10 kN/m² 40.80 kN/m² 45.00 kN/m²
(1) The overall classification based on the EN 12825 standard is determined by the load class value (Table 1) and the deflection class value (Table 2), as shown on pages 16-17 of the catalog. (2) Value not specified in the EN 12825 standard. (3) The distributed load is typically calculated by multiplying the concentrated load value by approximately 5.

Conversion data: 1 N = 0.1019 kg; 1 kN = 101.9 kg

DOWNLOAD AREA

Technical Data Sheet W30LZ

Complete Catalogue 2024

Talk to us

How can we assist you?

Alternative models

Frequently Asked Questions (FAQ)

What fire resistance does the GWI/S panel offer?

The GWI/S panel has a fire resistance of 120 minutes and is classified as A1FL for fire reaction, complying with UNI EN 13501-1 and 13501-2 standards.

What are the acoustic performance characteristics of the GWI/S panel?

The GWI/S offers airborne noise attenuation greater than 38 dB and impact noise reduction greater than 33 dB, in compliance with UNI EN ISO 140-12 and 140-8 standards.

Is it suitable for electrically sensitive environments?

Yes, the GWI/S panel complies with the EN 1081 standard and offers electrical resistance greater than 10^7 Ω, making it ideal for managing electrostatic charges.

What is the weight of the GWI/S panel without coverings?

The weight of the GWI/S panel without coverings is 18.3 kg, ensuring robustness and durability.

What type of load can the GWI/S panel support?

The GWI/S panel is designed to support concentrated loads up to 7.60 kN and distributed loads up to 45.00 kN/m², providing maximum reliability for the most demanding applications.

Other series

FF SERIES

GW SERIES

GW FUSION SERIES

TEST

DB SERIES

TG SERIES

Accedi per scaricare le risorse

Devi essere registrato per visualizzare questo contenuto.
Clicca qui per registrarti

sei già registrato? 
Effettua la Login